  Features
  Download PDF brochure

TCT - Trip Coil Tester

Designed specifically to enable HV circuit breaker trip coils to be tested at a reduced voltage.

  • Powered directly from the substation battery

  • Output precisely settable from 5 to 95% of battery voltage

  • Electronic regulation ensures guaranteed constant voltage during testing

  • 80A current capable

  • Trip-coil burnout protection

 

To ensure that circuit breaker operation is guaranteed under the most onerous conditions placed on the substation tripping supply, circuit breaker trip coils are specified to work with a minimum tripping voltage much below the nominal battery voltage. The minimum trip voltage test is described in a number of international and national standards such as IEC 56, ANSI C37.09 etc.

Traditionally, this test was performed by tapping the main tripping battery. This method however should not be utilised as it presents a considerable risk to testing personnel, battery and breaker being tested.

General purpose DC sources as well as variac-based instruments are also unsuitable due to their inability to maintain their output voltage precisely regulated at the high peak currents drawn by trip-coils. 

The TCT contains a very high speed electronic voltage regulator which will accurately maintain the output voltage constant whilst very high peak currents are drawn, for a period long enough to allow the operation of the trip coil. The precise level of test voltage during the entire test is always known and guaranteed constant.


Features

Input

  • Ultra-wide 20 to 280 Vdc input voltage operating range. Works with all tripping supply voltages used worldwide 

Output

  • User settable from 5 to 95% of input voltage via multi-turn dial
  • Precisely regulated to set value (2% max deviation) 
  • Powerful 80A capability

Voltmeter

  • 0-300Vdc measuring range
  • LCD, 4.5 digit Autoranging with backlight
  • Measures both Input and Output voltages

Protections   

  • Reverse polarity
  • Output overload. Shutdown when current >80A
  • External voltages on output

Trip-Coil Burnout Protection

  • Shutdown and warning when trip-coil draws current continuously for >500 msec

Regulation fail Detector

  • Independently monitors output and warns user if output voltage did not remain within 2% of set value for whatever reason

Misc

  • Field proven rugged design, in worldwide use
  • Weight: 8.2Kg
  • Case: IP65 Rated, 308x206x206 mm, 3mm Aluminium Shell