         DESCRIPTION

  • The PMAC720 Multifunction Power Meter provide high accuracy measurement,display and communication (Modbus RTU) of all electrical and power quality parameters.
  • They also have digital inputs and outputs and interface with versatile functions such as alarms.
  • Harmonic measurement up to 31st.
  • RS485 Communication, standard MODBUS protocol.
  • Maximum and minimum of instant measurement.
  • Optional Clock and SOE event Log Function.
  • TOU ( Time of Use Function )
  • Achieving the Class-1 measuring accuracy by IEC62053.
  • Large high contrast LCD screen easy for operating and setting with password lock.   Digits LCD Color Black.   Background : Color Green   

        APPLICATIONS

  • Control Panel and Motor, Generator monitoring
  • Switchgear distribution Systems.
  • Energy Management
  • Power Quality Analysis.
 

Order Information
Model: PMAC720 - Code 1 - Code 2 - Code 3 - Code 4 - Code 5 - Code 6 - Code 7

CODE 1  

N

A

B

C

D

E

Basic Module

Basic Module + 4 Status Inputs ( Dry Contact ) + 4 Relay Output Ports 

Basic Module + 8 Status Inputs ( Dry Contact ) + 2 Relay Output Ports

Basic Mod.+ 4 Status Inputs(External Voltage Required)+2 Relay Output Ports

Basic Mod.+ 8 Status Inputs(External Voltage Required)+2 Relay Output Ports

Basic Module+ 2 Pulse Outputs + 2 ( 4 ~ 20mA ) Analog Outputs  

CODE 2  

H

 Up to 31st Harmonic
CODE 3  

T

 Clock and SOE ( Event Log ) Function
CODE 4  

F

 TOU ( Time of Use )
CODE 5  

M

Two RS485 Communication Ports.
CODE 6  

AI

 One 4 ~ 20mA  Analog Input

AO

 One 4 ~ 20mA  Analog Output
CODE 7  

V1

 Rated Voltage / Current Input : 57.7 / 100V, 5A

V2

 Rated Voltage / Current Input : 57.7 / 100V, 1A

V3

 Rated Voltage / Current Input : 220 / 380V, 5A

V4

 Rated Voltage / Current Input : 220 / 380V, 1A
                  DATA SHEET                          QUOTATION

 

 Note :  

  Basic Module Functions:  
  Measurement 3 Phase Current / Voltages, Neutral, Phase Current, 3 Phase
  Active Power / 3 Phase Reactive Power, Total Active Power, Total reactive
  Power, Frequency, 3 Phase Power Factor, Total Power Factor, Active Energy
  Reactive Energy, It contains ONE RS485 communication port originally.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 