Industry standard inputs are provided for
connection to a sub-standard and meter pickup-heads. Alternatively,
software programmable inputs allow meter pulse signals of any type
(dry contact or voltage pulses from 2V to 250V) to be used.
The APTS test set provides
the voltage and current sources to drive the meters under
test.
Once the
Meter Test Interface is connected, the APTS software program
provides for either totally automatic or manual meter testing to
take place. The meter testing module of the APTS software includes
comprehensive results
archiving, presentation and printing facilities as well as
error/trend analysis.
APTS GPS
Interface
| The APTS GPS
Interface enables two or more physically separated APTS test
sets to be triggered at precisely the same instant in
time.
It is
used principally when performing end-to-end tests on line
protection schemes. |
 |
The APTS
GPS Interface consists of a rugged waterproof GPS integrated
receiver/aerial unit and a small connector mounted enclosure which
plugs into the APTS interface connector. A 100ft (30m) cable allows
the receiver/aerial unit to be optimally positioned outdoors.
The receiver/aerial unit utilised is an application-specific
high-noise immunity precision timing receiver with guaranteed timing
accuracy.
In use, the
APTS software displays the current GPS time, date and location. The
user enters the time and date at which it is desired to generate the
trigger event. The trigger event so
set-up can be used to initiate any APTS test, including end-to-end
and DFR/COMTRADE/EMTP replay. UTC time is used at all times,
facilitating use across differing time zones. At the end of a test,
the trigger event time, date and location information from the GPS
Interface is saved as part of the results file.
The GPS Interface is powered directly by the APTS
test set. Digital trigger inputs and outputs are also available and
these can be programmed for specialist functions, like the precise
high-resolution absolute time-tagging of external event inputs and
the generation of timed event outputs.
Specifications
- Trigger pulse accuracy:
- Total System trigger accuracy:
- Acquisition time:
|
±200ns from programmed UTC trigger
time ±50µs <3 minutes (typical, cold start to full
specs) |
CT Magnetising Curve
Interface
This
accessory permits the APTS to be used for testing power system
protection current transformers. The interface plugs into the
APTS voltage outputs so that the three APTS voltage
amplifiers are connected in series, thus producing a single 0-900
Vac output. This voltage is fed to the CT secondary. A current
transducer in the interface measures the magnetising current.
The interface enables the APTS test set to automatically plot the
magnetising curve of the CT under test.
|