- Third generation of the time-proven ORTS relay tester
- 2000VA total high power / high burden outputs
- Latest low-distortion, low-loss all-switchmode Digital Signal
Processing based technology
- 0-100A main output
- Switchable 0-140V or 0-10A auxiliary output (0-360º phase
shiftable)
- 0-260Vdc battery simulator (for powering static relays)
- Ideal for Traction/Railway and general Distribution relay
testing
The ORTS is a multipurpose single-phase field-portable
protection relay test set capable of automatically testing a very
wide range of relays, from high-burden eletromechanical types to the
latest solid-state microprocessor-based models. The supplied Windows
based software fully controls the test set from any suitable laptop
computer.
|
Relays
tested
-
Induction Disc
Overcurrent (high burden CDG etc.)
-
Directional
Overcurrent
-
Instantaneous
Overcurrent
-
Under/Over
Voltage
-
Under/Over
Frequency
-
Rate of Change of
Frequency (ROCOF)
-
Transformer/Generator
Differential
-
Distance (single-phase
Traction-types, e.g. Optimho etc.)
-
Thermal relays
| Features - Software
- Total test set control from any Windows 95/98/NT/2000/XP based PC
- Full results archiving, display and printing facilities
- Fully Automatic or Manual
Control.
- Error and Trend analysis of test results
- Results are fully traceable to test
set hardware, software and calibration data.
Features - Hardware
|
Main Output
- 0-100A @ ±34Vpk or
0-10A @
±340Vpk
- 1500VA continuous
- 0.01A/0.001A Resolution
|
Auxiliary Output
- 0-140V or
0-10A @ ±190Vpk
- 300VA continuous
- 0.01V/0.001A Resolution
|
|
Frequency
- 45.000-64.999 Hz Range
(freq
lockable to input supply)
- +/-0.001 Hz Resolution
- < +/- 0.005% Error
|
Phase Angle
- 0-360º Range
- +/- 0.1 Resolution
- < +/- 0.1º Error
|
|
Accuracy / Distortion (all
outputs)
- < +/- 0.5% Error
- < 0.2% Distortion
|
DC Supply Output
(battery simulator)
- 0-260Vdc
- 200VA continuous
- 0.01V Resolution
|
|
Contact In
- 4x independent and isolated contact
inputs
- Software selectable as wet/dry, contact or
2.5-250V AC/DC voltage sensing
- ±0.1msec timing resolution
|
Contact
Out
- 4x independent and isolated contact
outputs
- Rated 10A@250Vac/1A@120Vdc
|
|
Protections
- All outputs are individually
monitored for overload, short/open circuit, over-temperature
and waveform accuracy
|
Input
Power
- Universal Supply: Fully
Automatic 90-260V 45-65Hz AC, 200W no load, 2400W continuous
max, overload and thermal protection
- Active Electronic Power Factor Correction
(CosΦ>0.99)
|
|
General
- Every input & output is
galvanically isolated from each other and chassis
- Isolated RS232 interface for
relay comms
- Parallel interface for control from any
standard PC/Laptop parallel printer port
- Physical:
380x210x400mm (not including handle),
Weight: 19.9Kg
- Environmental: 0-50°C Operating
Temperature, IP20 Protected Enclosure
CE Marked, Tested
to EN50081-2 (emissions) & EN50082-2
(susceptibility) |
|
Ask
for ORTS demo
program
Ask for the full brochure - ORTS3brochure.PDF
(0.5Mb)
Download FREE PDF reader
|